25
Protection Over current protection & Over charging voltage protection (SCR control)
Thermal protection (CPU control):When temperature inside INVERTER AND
UPS is over 45℃, charger will stop charging for 2.5 minutes followed by an 1.5
minutes charging. The cycle will be repeated until the temperature is lower
than 44℃.
Monitoring Smart monitoring & warning for failed battery or open-circuit battery.
Auto-detection each time when power on or every 6 days.
Communications & Management
Standard Interface port UPSilon2000 compatible
RS232 (USB port is optional)
Optional Interface part RJ45 (Surge protection), DB9, SNMP
Control panel LCD or LED Selectable
Audible alarm
Alarm on battery:Low battery & Battery over voltage
Alarm on abnormal operation:Over load, Short-circuit, & Over heat
EBT (Estimation of
Backup Time) system
Support for LCD display
Green mode function
(Auto-shutdown during
blackout)
1% to 14% of full load (adjustable by using the remote set-up software)
The default setting is OFF.
Cooling fan control Auto on / off, controlled by temperature & operation mode
Environmental and Safety
Operating Temperature
Up to 1500 meters:0 to 40 (32 to 104 )℃℃℉ ℉
Transit/storage
Temperature
-15 to 55 (5 to 131 )℃℃℉ ℉
Relative Humidity 5 - 95% non condensing
Operating Altitude 0 ~ 3000 meters
Audible noise at 1M from
surface of unit
≦50 dBA
Isolation 3KVac for 1 minute between battery and AC side
Quality control system ISO 9001