120V Models 230V Models
Nominal Voltage 100V/110V/120V Selectable 220V/230V/240V Selectable
Input Frequency 47Hz ~ 65Hz, 50/60Hz auto-sensing
Efficiency 97% (Normal mode)
Noise Filtering Full time EMI/RFI filtering
Over current protection
IS1100LTby AC fuse
IS2200LT / IS3000LT
by re-settable over current protector
IS1100LT / IS2200LTby AC fuse
IS3000LT / IS5000LTby
re-settable over current protector
Voltage Range -20% ~ +22% for selected nominal voltage.
-29% ~ +33% adjustable by using the remote set-up software
AVR Range
(2 Bucks, 2 Boosts)
Enhanced Buck: +15% of selected nominal voltage
Buck mode: +5% of selected nominal voltage
Boost mode: -5% of selected nominal voltage
Enhanced Boost: -12.5% of selected nominal voltage
Surge Protection
IS1100LT220 Joules
IS2200LT440 Joules
IS3000LT / IS5000LT660 Joules
Battery
Battery type
Lead-Acid 25Ah 250Ah
IS1100LT(1100VA/ 660W) : 24Vdc (48Vdc optional)
IS2200LT(2200VA/ 1350W) : 48Vdc (24/36Vdc optional)
IS3000LT(3000VA/ 1800W) : 72Vdc (24/36/48Vdc optional)
Voltage
N / A IS5000LT(5000VA/ 3200W) : 48Vdc
Typical backup time No Limit
Charging method
Smart pulse charging with two charging modesQuick charging when battery is
not fully charged, trickle charging when battery is 90% fully charged.
Charging current 11A for IS1100LT / IS2200LT / IS3000LT
30A for IS5000LT(48Vdc)
20A Optional for IS1100LT / IS2200LT / IS3000LT(Below 48Vdc)
P.S. At normal line and normal temperature (Average)
Average charging
voltage for each battery
Quick charging mode14V maximum.
Trickle charging mode13.2V ~ 13.9V adjustable with the remote set-up
software.